Bubble-tight Isolation Damper

  • The test set up complies with ASME N509 & N510 1995 (“Testing of Nuclear Air Treatment Systems”). Measurements were taken in general accordance to AMCA 500-D.
  • Housing leak tested at 3800 Pa with leak rate 0.0005 CFM per cubic foot of housing volume.
  • Blade and shaft seals tested in the closed position at 2500 Pa, leakage rate < 0.029 CFM per inch of circumference of blade.